2

Share:


5HP Food Processing Water Chiller – Air-Cooled

KF-LF5A 5HP Air-Cooled Water Chiller for Food Processing

The KF-LF5A Food Industry Air-Cooled Chiller is an industrial water chiller with a 5HP Panasonic hermetic scroll compressor, supplied by MEKAHSA MACHINERY SDN BHD in Kuala Lumpur, Malaysia. It supplies cooling water to compatible food mixers and processing equipment, with stainless steel pump and connection options available for project-specific requirements.

The unit operates on 415V / 50Hz / 3-phase power and has a specified temperature range of 3°C to 35°C. Share your process heat load, target water temperature and required cooling time so we can review the configuration for your application.

Technical Specifications

KF-LF5A Technical Specifications
Model KF-LF5A
Power supply 415V / 50Hz / 3 Phase
Temperature range 3°C – 35°C
Total power consumption 10 kW
Cooling capacity 11,223 kcal/h (approximately 13 kW)
Compressor type Hermetic scroll type
Compressor capacity 5 HP
Compressor brand Panasonic
Compressor quantity 1 unit
Condenser type High-efficiency copper tube with V-shape aluminium fins and low-noise outer rotor fan
Condenser air volume 5,000 m³/h
Evaporator type High-efficiency mild steel shell and stainless steel tube evaporator
Cooling water flow 2.24 m³/h
Water inlet and outlet size 1 inch
Refrigerant R410A
Refrigerant control External balanced expansion valve
Water pump power 0.75 kW / 1 HP
Water pump upgrade Stainless steel pump option
Water pump flow rate 123 L/min
Water pump head / lift 22 m
Machine dimensions (L × W × H) 1490 × 720 × 1150 mm
Approximate machine weight 200 kg

Specifications apply to the stated KF-LF5A configuration. Confirm the final equipment specification and performance at your required water temperature and site conditions before ordering. Cooling-water flow and pump flow are separate specification entries; operating flow depends on the system arrangement. The listed pump flow and head should not be assumed to occur simultaneously without checking the pump curve.

Stainless Steel Options for the Water Circuit

  • 1HP stainless steel water pump upgrade: Specify the required water-contact materials when ordering.
  • Stainless steel inlet and outlet connections: Available as a customised configuration, as demonstrated in our Shah Alam food industry project.
  • Material confirmation: Confirm stainless steel grade, wetted parts and seals against the intended water quality and cleaning conditions.

The evaporator specification is a mild steel shell with stainless steel tubes. The materials of individual components should be checked when specifying the complete water circuit. Stainless steel options do not by themselves establish suitability for direct food contact.

Protection Features

  • Overload protection
  • Overheat protection
  • Phase failure protection
  • High/low pressure protection
  • Water flow protection
  • Anti-freezing protection

Food Processing Application: Shah Alam Project

A food industry customer in Shah Alam selected a customised 5HP air-cooled chiller to cool water in a one-tonne tank, approximately 1,000 litres, for distribution to food mixers and processing equipment. The project included stainless steel inlet and outlet connections and a 1HP stainless steel water pump, followed by safe delivery to the customer's factory.

Tank volume alone does not determine the required chiller size. Starting and target temperatures, cooling time, production heat load and water flow must also be considered.

View the Shah Alam food industry chiller project and read our food processing water chiller application guide.

Supply and Delivery Scope

Request a quotation for one KF-LF5A chiller with your selected configuration. The final quotation should identify the stainless steel upgrades, delivery destination and agreed scope of supply.

Confirm whether external water tanks, site pipework, electrical connections, unloading, installation and commissioning are required and included in your quotation. Delivery charges, lead time and warranty terms should also be agreed before ordering. The one-tonne tank described in the project case is part of that customer's application and is not an automatic inclusion with every chiller.

Frequently Asked Questions

Does 5HP mean 5HP of cooling capacity?

The 5HP specification refers to the compressor capacity designation. Chiller selection should use the stated cooling performance at the relevant operating conditions, together with the process heat load.

Can the water pump and connections be upgraded to stainless steel?

Yes. A 1HP stainless steel pump and customised stainless steel inlet and outlet connections can be specified. Confirm the exact component materials and selected options in the quotation.

Can this chiller cool a 1,000-litre tank?

A 5HP configuration was selected for the Shah Alam project using an approximately 1,000-litre tank. Suitability for another tank depends on the required temperature, cooling time and heat added during production.

Request a KF-LF5A Chiller Quotation

Send your equipment details, tank volume, starting and target temperatures, required cooling time, water flow requirements, available power supply and factory location. Include any stainless steel requirements and whether the cooling water is separate from or in direct contact with food.

WhatsApp MEKAHSA: +6018-371 5359 or contact our team to discuss the configuration and delivery scope.



 Inquiry - 5HP Food Processing Water Chiller – Air-Cooled